Engineering guide
Every Liebert EXL S1 message has a display ID. In Vertiv's SL-26090 guide, alarm IDs start with 2 and fault IDs start with 3: 24-012 Battery under voltage is an alarm that stops the inverter, while 32-028 Rectifier Temperature fault is a fault set at 95 °C by default. The tables below explain the codes operators see most, and which ones need a technician.

3:06. On a Vertiv Liebert EXL S1, every message has a display ID: in the maker's tables, alarm IDs start with a 2 and fault IDs start with a 3, so the first digit already tells you which table to look in. This video walks the battery, supply, load, heat and fault codes operators see most, with the maker's code names and our advice where the guide is silent, from the Liebert EXL S1 guide SL-26090 Appendix A.
0:00 What does a fault code on a Liebert EXL S1 mean? What does a fault code on a Liebert EXL S1 mean? Every message has a display ID. In the maker tables, alarm IDs start with a 2, and fault IDs start with a 3, so the first digit already tells you which table to look in.
0:15 Where do you read it? Where do you read it? The maker guide lists every message in its appendix tables: status, alarms, and faults. Each line gives the component, the text on the display, and a display ID such as 24-012.
0:28 Which battery alarms will you see? Which battery alarms will you see? Battery under voltage, 24-012, means the battery voltage is below the shutdown voltage, and this warning stops the inverter. Battery Is Not Connected, 24-064, and BCB Breaker Open, 24-068, mean there is no battery backup until the breaker is closed.
0:50 What do the supply and load alarms mean? What do the supply and load alarms mean? Bypass mains failure, 21-013, and rectifier mains failure, 22-015, mean a supply has failed after a set delay. Inverter overload, 26-031, means the overload timeout has reached 100 percent, and with the default configuration the UPS requests a transfer to bypass.
1:14 Which alarms point at heat and airflow? Which alarms point at heat and airflow? Overtemperature Phase UA, 22-061, means the rectifier phase temperature is above its setting, 80 degrees Celsius by default. Input Air High Temperature, 20-027, and the I/O transformer overtemperature alarm point at room cooling and load. A fan failure alarm means a fan has failed.
1:37 Which faults need a technician before any restart? Which faults need a technician before any restart? Overload, 36-046, means the inverter RMS overload counter has run out: reduce the load before any restart. Rectifier Temperature fault, 32-028, is set at 95 degrees Celsius by default. Battery Test Failure, 34-023: the battery test failed. Our advice: book a block-by-block string test. And Fuse Blown Phase UA, 36-080, needs a technician.
2:08 What can you check safely? What can you check safely? Read the code and note the time. Check room cooling, airflow, and the load on the output. Where the code points at wiring or phase rotation, correction is electrician work. A ground fault alarm and CAN Communication Loss, 28-008, which means no CAN messages for 10 seconds: do not open the cabinets or work on live parts; note the message and call a technician. Two more worth knowing. System Maint. Bypass Switch Closed, 20-019, means the load is on utility power without conditioning. And repeated battery alarms, under voltage or test failure, usually end in a string replacement. If you are servicing an EXL S1, request a quote at threephaseups.ca.
Vertiv's EXL S1 operation and maintenance guide, SL-26090, lists every message in Appendix A in three tables: status, alarms and faults. Each line gives the component, the text on the display and a display ID such as 24-012. In those tables, every alarm ID starts with a 2 and every fault ID with a 3, so the first digit already tells you which table to look in.
| Message (ID) | What Vertiv's manual says | What you can check |
|---|---|---|
| Battery under voltage (24-012) | The battery voltage is below the shutdown voltage; this warning stops the inverter. | Whether the UPS is on battery and how long the outage has lasted. |
| Battery Is Not Connected (24-064) | The battery is not connected. | Whether the battery breaker was left open after work. |
| BCB Breaker Open (24-068) | The battery circuit breaker is open. | Whether it was opened on purpose; until it is closed, there is no battery backup. |
| Bypass mains failure (21-013) | The bypass supply has failed, after a set delay. | The breaker feeding the bypass input. |
| Bypass Wrong Phase Rotation (21-083) | The bypass input phase rotation is wrong. | Whether upstream electrical work was done. Correction is electrician work. |
| Rectifier mains failure (22-015) | The rectifier input supply has failed, after a set delay. | Whether the site has an outage or a tripped feeder. |
| Wrong phase rotation (22-017) | The input line phase rotation is incorrect. | Same as the bypass case: an electrician corrects it. |
| Overtemperature Phase U-A (22-061) | Rectifier phase temperature is above its setting, 80 °C by default. | Room temperature and airflow. |
| Inverter overload (26-031) | The overload timeout has reached 100%; with the default configuration this requests a transfer to bypass. | The load on the output and anything added recently. |
| System Maint. Bypass Switch Closed (20-019) | The system maintenance bypass switch is closed. | Whether maintenance is under way; the load is on unconditioned utility power. |
| Input Air High Temperature (20-027) | The incoming air is too hot. | Room cooling and blocked intakes. |
| Fan Failure Phase U (20-210) | A fan has failed (phases U, V, W and other locations have their own IDs). | Book a fan replacement. |
| I/O Transformer Overtemperature (20-224) | An input or output transformer is too hot. | Load level and room temperature. |
| AC Ground Fault (20-133) | A ground fault has been detected on the AC side. | Do not open the cabinets or work on live parts; note the message and call a technician. |
| CAN Communication Loss (28-008) | Internal CAN messages have not been received for 10 seconds. | Do not open the cabinets or work on live parts; note the message and call a technician. |
| Message (ID) | What Vertiv's manual says | What you can check |
|---|---|---|
| Battery Test Failure (34-023) | The battery test has failed. | Book a string test block by block. |
| Battery Ground Fault (34-071) | The battery ground fault detector has tripped. | Do not open the cabinets or work on live parts; note the message and call a technician. |
| Back-feed protection (31-023) | A back-feed fault has been detected. | Do not open the cabinets or work on live parts; note the message and call a technician. |
| Overload (36-046) | The inverter RMS overload counter has run out. | Reduce the load before any restart. |
| Fuse Blown Phase U-A (36-080) | An inverter output fuse is open (phases V and W have their own IDs). | Do not open the cabinets or work on live parts; note the message and call a technician. |
| Rectifier Temperature fault (32-028) | Rectifier phase temperature is above its fault setting, 95 °C by default. | Room cooling first; the fault itself needs a technician. |
| Parallel cable missing (30-071) | A parallel cable is missing. | Do not open the cabinets or work on live parts; note the message and call a technician. |
| High Ambient Temperature (30-202) | The ambient temperature is too high. | Room cooling. |
Battery under voltage, Battery Test Failure and repeated BCB alarms usually end in a string replacement. EXL S1 sites typically fall under our high-capacity three-phase service, and blocks for Liebert cabinets are listed with the Liebert and Vertiv batteries.
The initial start-up of a new EXL S1 is done by Vertiv; we do not commission new large Vertiv systems. The tables above are for units in service.
Battery under voltage: the battery voltage is below the shutdown voltage, and the warning stops the inverter. Check whether the UPS is on battery and whether the utility is back.
By the first digit of the display ID in Vertiv's tables: alarm IDs start with 2, fault IDs with 3.
Vertiv's guide gives a default of 80 °C for the rectifier phase overtemperature alarm (22-061) and 95 °C for the rectifier temperature fault (32-028).
The maintenance bypass switch is closed, so the load runs on utility power without UPS conditioning or battery backup. It is expected during maintenance and should be cleared afterwards.
Note the code and the time first. Faults such as 36-080 Fuse Blown or 34-071 Battery Ground Fault need a technician before any restart.
Sources, checked October 4, 2026: